Free Voltage Drop Calculator Canada — Wire Size & Distance
Calculate exact voltage drop (V and %), terminal load voltage, and minimum recommended wire gauge (AWG / kcmil) for Canadian 120V, 208V, 240V, 347V, and 600V Copper or Aluminum circuits.
1. Circuit Voltage, Load, Wire Size & Length
Transparent Voltage Drop Formula (75°C Reference):
• Formula: VD = (2 × K × I × D_ft) / CM
• Calculation: (2 × 12.9 × 30A × 125.0 ft) / 10,380 CM = 9.32V (3.88%)
Bow River Electrical & Controls Ltd.
Panel B → Sub-Panel Garage / EV Charger (30A)
PF: 0.9 · Copper (10 AWG)
| Conductor Size & Circular Mils (CM) | 10 AWG (10,380 CM) |
| One-Way Run Length | 125.0 ft (38.1 m) |
| Resistivity Constant (K at 75°C) | 12.9 Ω·CM/ft (Cu) |
| Max One-Way Distance for 10 AWG to Stay ≤ 3.0% | 97 ft (29.4 m) |
Export Voltage Drop Calculation Sheet (PDF)
Save for electrical permit submittals or panel schedules.